APC Smart-UPS RT 3000VA 230V 2100W, SURTD3000XLI

Gọi để biết giá (giá chưa bao gồm VAT)

Model: APC Smart-UPS RT 3000VA 230V

Part #: SURTD3000XLI

– APC Smart-UPS RT, 3000VA/2100W, Input 230V/Output 230V, Interface Port DB-9 RS-232, SmartSlot, Extended runtime model, Rack Height 3 U

– Typical Backup Time at Full Load 14.1 minutes (2100 Watts)

Includes: CD with software, Smart UPS signalling RS-232 cable, User Manual

Hãng sản xuất: APC
Tình trạng: Mới
Bảo hành: 24 tháng chính hãng

Mua hàng

Thông tin sản phẩm APC Smart-UPS RT 3000VA 230V 2100W, SURTD3000XLI

Output

Output Power Capacity 2100 Watts / 3000 VA

Max Configurable Power 2100 Watts / 3000 VA

Nominal Output Voltage 230V

Output Voltage Note Configurable for 220 : 230 or 240 nominal output voltage

Output Voltage Distortion Less than 3%

Output Frequency (sync to mains) 50/60 Hz +/- 3 Hz user adjustable +/- 0.1

Other Output Voltages 220,240

Crest Factor 3 : 1

Waveform Type Sine wave

Output Connections

(8) IEC 320 C13

(2) IEC 320 C19

(2) IEC Jumpers

Bypass Internal Bypass (Automatic and Manual)

Input

Nominal Input Voltage 230V

Input Frequency 50/60 Hz +/- 5 Hz (auto sensing)

Input Connections

British BS1363A

IEC-320 C20

Schuko CEE 7/EU1-16P

Cord Length 2.44 meters

Input voltage range for main operations 160 – 280V

Input voltage adjustable range for mains operation 100 – 280V

Other Input Voltages 220,240

Batteries & Runtime

Battery Type Maintenance-free sealed Lead-Acid battery with suspended electrolyte : leakproof

Included Battery Modules 2

Typical recharge time 2.50 hour(s)

Replacement Battery RBC44

RBC™ Quantity 1

Extended Run Options APC Smart-UPS RT 3000VA 230V

Runtime Graph

Curve    Part Number(s)

A             SURTD3000XLI

B             SURTD3000XLI

+ (1)SURT192XLBP

C             SURTD3000XLI

+ (2)SURT192XLBP

D             SURTD3000XLI

+ (3)SURT192XLBP

E              SURTD3000XLI

+ (4)SURT192XLBP

Hover over the line on the graph above to view the runtime at any desired load

Curve fit to measured runtime data. All measurements taken with new, fully charged batteries, at typical environmental conditions, with no electrical input and balanced resistive load (PF = 1.0) output.

View Enlarged Graph View Runtime Chart

Energy Use/Efficiency

Load      Efficiency

25%        87.6%

50%        91.2%

75%        92.0%

100%     92.0%

Hover over the line on the graph above to view the efficiency at any desired load

Curve fit to measured efficiency data. All measurements taken in normal operating mode, at typical environmental conditions, with nominal electrical input and balanced resistive load (PF = 1.0) output.

View Enlarged Chart

Communications & Management

Interface Port(s) RJ-45 Serial,Smart-Slot

Available SmartSlot™ Interface Quantity 1

Control panel LED status display with load and battery bar-graphs and On Line : On Battery : Replace Battery : Overload and Bypass Indicators

Audible Alarm Alarm when on battery : distinctive low battery alarm : overload continuous tone alarm

Emergency Power Off (EPO) Yes

Surge Protection and Filtering

Surge energy rating 480 Joules

Filtering Full time multi-pole noise filtering : 0.3% IEEE surge let-through : zero clamping response time : meets UL 1449

Physical

Maximum Height 432.00 mm

Maximum Width 130.00 mm

Maximum Depth 660.00 mm

Rack Height 3U

Net Weight 54.55 KG

Shipping Weight 63.64 KG

Shipping Height 347.00 mm

Shipping Width 603.00 mm

Shipping Depth 980.00 mm

Color Black

Units per Pallet 6.00

Environmental

Operating Environment 0 – 40 °C

Operating Relative Humidity 0 – 95%

Operating Elevation 0-3000 meters

Storage Temperature -15 – 45 °C

Storage Relative Humidity 0 – 95%

Storage Elevation 0-15000 meters

Audible noise at 1 meter from surface of unit 55.00 dBA

Online Thermal Dissipation 609.00 BTU/hr